The phenomenon of on-load corrosion is directly associated with the production of magnetite on the water-side surface of boiler tubes. On-load corrosion may first be manifested by the sudden, violent rupture of a boiler tube, such failures being found to occur predominantly on the fire-side surface of tubes situated in zones exposed to radiant heat where high rates of heat transfer pertain. In most instances, a large number of adjacent tubes are found to have suffered, the affected zone frequently extending in a horizontal band across the boiler. In some instances, pronounced local attack has taken place at butt...