Skip to Main Content
ASM Failure Analysis Case Histories

Handbook of Case Histories in Failure Analysis

Edited by
Khlefa A. Esaklul
Khlefa A. Esaklul
Search for other works by this author on:
ASM International
Volume
1
ISBN electronic:
978-1-62708-214-3
Publication date:
1992
Book Chapter

Failure of an Aluminum Connector in an Electrical Transmission Cable

By
H.C. Furtado
H.C. Furtado
CEPEL Electrical Energy Research Center
Search for other works by this author on:
;
W.A. Mannheimer
W.A. Mannheimer
CEPEL Electrical Energy Research Center
Search for other works by this author on:
Published:
1992
Page range:
428 - 430

Abstract

An 1100 aluminum alloy connector of a high-tension aluminum conductor steel-reinforced (ACSR) transmission cable failed after more than 20 years in service, in a region of consider able industrial pollution. The steel core was spliced with a galvanized 1020 carbon steel sheath. Visual examination showed that the connector had undergone considerable plastic deformation and necking before fracture. The steel sheath was severely corroded, and the steel splice was pressed off-center in the axial direction inside the connector. Examination of the fracture surface and micro-structural analysis indicated that the failure was caused by mechanical overload, which occurred because of weakening of the steel support cable by corrosion inside the fitting. The corrosion was ascribed to defective assembly of the connector which allowed moisture penetration.

You do not currently have access to this content.
Don't already have an account? Register

H.C. Furtado, W.A. Mannheimer, 1992. "Failure of an Aluminum Connector in an Electrical Transmission Cable", Handbook of Case Histories in Failure Analysis, Khlefa A. Esaklul

Download citation file:


Close
Close Modal
This Feature Is Available To Subscribers Only

Sign In or Create an Account

Close Modal
Close Modal