Various aluminum bronze valves and fittings on the essential cooling water system at a nuclear plant were found to be leaking. The leakage was limited to small-bore socket-welded components. Four specimens were examined: three castings (an ASME SB-148 CA 952 elbow from a small-bore fitting and two ASME SB-148 CA 954 valve bodies) and an entire valve assembly. The leaks were found to be in the socket-weld crevice area and had resulted from dealloying. It was recommended that the weld joint geometry be modified.

You do not currently have access to this chapter.
Don't already have an account? Register

Carl J. Czajkowski, 1993. "Dealloying in Aluminum Bronze Components", Handbook of Case Histories in Failure Analysis, Khlefa A. Esaklul