Skip to Main Content

Abstract

Six cracked A36 steel gusset plates that formed part of the roof trusses of a large manufacturing facility were discovered during a routine final inspection of a new building construction. Two different-size plates from different locations in the building were removed and tested. It was determined that the gusset plates failed in the heat-affected zone via an intergranular microcracking mode due to hydrogen-assisted underbead and toe-weld cracking. Proper nondestructive testing techniques for magnetic particle and radiographic inspection of the plate-weld gusset areas were recommended.

You do not currently have access to this chapter.
Don't already have an account? Register

William F. Jones, III, 1992. "Hydrogen-Induced Cracking of Welded Truss Gusset Plates", Handbook of Case Histories in Failure Analysis, Khlefa A. Esaklul